Location
Type
Size
Sewer
Remarks
(mm)
Machine Room
B
80
S/ST
Mechanical Equipment Rm
B
100
S
With 1/2 grate when
adjacent to
equipment
Miscellaneous Areas:
Finished Walk Areaway
B
100
ST
Window Well Areaway
B
80
ST
Legend:
S = Sanitary Sewer
ST = Storm Sewer
NB = Nickel Bronze
Types:
B-CI W/NB Grate
M-NB Funnel Strainer
C-Finished Areas
O-300 mm (12") Square
D-Latex Mastic Floors/Thin Set Tile
S-300 mm (12") Square w/Grate 1
NOTES:
1.
Floor drains for general floor drainage are located by architect.
Use Type "C" in finished areas.
2.
Provide trap primer for all drains not receiving a direct discharge.
3.
SI Conversion: 50 mm = 2", 80 mm = 3", and 100 mm = 4".
16.
See Master Specification 15200 for base and isolator description.
Minimum deflections indicated as millimeters.
Equipment
Equipment Location
On Grade
6 m (20 ft.)
9 m (30 ft.)
Floor Span
Floor Span
Base
Isol
Min.
Base
Isol
Min.
Base
Isol
Min.
Type
Type
Defl
Type
Type
Defl
Type
Type
Defl
PUMPS
Close Coupled
Up to 1200 W
--
--
--
--
D, L,
--
--
D, L,
--
(1-1/2 HP)
W
W
Over 1200 W
--
--
--
I
S
25
I
S
25
(1-1/2 HP)
Base Mounted
Up to 7500 W
--
--
--
--
D, L,
--
--
D, L,
--
(10 HP)
W
W
11