06-06
1. Mechanical Cooling: The designer shall coordinate the need to
maintain lower space temperature in the equipment room for proper
functioning of the associated electronic equipment; and, provide a
dedicated, standalone cooling unit, if required. The unit shall be
DX, air cooled to ensure an easy start in mild weather.
2. Ventilation: If mechanical cooling is not required, a
thermostatically controlled, dedicated ventilation system shall be
provided to remove heat gain generated due to the elevator
equipment. The system shall comprise of an exhaust fan, motorized
intake louver (if the machine room has an external wall or an
exposed roof), or a supply air make-up fan. Air distribution
ductwork on the exhaust and intake side shall be provided as
required.
3. Heating: To maintain the minimum design winter temperature, a
thermostatically controlled electric unit heater shall be
provided.
4. Life Safety Code NFPA 101 requires that when stand-by power is
connected to the elevator, the machine room ventilation or air-
conditioning shall also be connected to stand-by power; exception:
D. MECHANICAL EQUIPMENT ROOM:
1. Ventilation: A thermostatically controlled ventilation system,
with features similar to the elevator equipment room ventilation
shall be provided to prevent excessive space temperature.
2. Heating: To maintain the minimum design winter temperature, a
thermostatically controlled unit heater (hot water or steam
preferred) shall be provided. Note that it may not be necessary to
provide any heat in the equipment rooms where steam system
components, such as, pressure reducing valve station and/or steam
to hot water convertors are located.
E. TRANSFORMER ROOM: Similar to Item D above. The space heat gain due to
the transformer losses shall be calculated based on the KVA ratings
and type of transformers. Use the following estimate as a guide:
1. Dry Type Transformers: 35 W (120 BTUH) per KVA for 30 KVA to 112
KVA sizes.
2. Liquid Type Transformers: 15 W (50 BTUH) per KVA for 225 KVA and
larger sizes.
3. Electrical Equipment Rooms (Switchgear Rooms): Same as Paragraph D
above.
16