Summer
Winter
Room or Area
Db Degrees C
RH
Db Degrees C
RH
(Degrees F)
Percent
(Degrees F)
Percent
Therapeutic Pools
26(80)-29(85)
--
29 (85)
--
39 (104)
(Maximum)
Treatment Rooms
24 (76)
50
25 (78)
30
Warehouses
Ventilation Only
15 (60)
--
*TERMINOLOGY OF SPECIAL PROCEDURE ROOMS:
Bronchoscopy: Examination of the bronchi (air passage of the lungs)
through a bronchoscope.
Cardiac Catheterization: Employment of a small catheter through a
vein in an arm, leg or neck and into the heart.
Colonoscopy: Examination of the entire colon with a colonscope.
EGD (Esophagogastroduodenoscopy): Endoscopic examination of the
esophagus and stomach, and duodenum (small intestine).
Cystoscopy: Direct visual examination of the urinary tract with a
cystoscope.
Endoscopy: Examination of organs such as the bladder, accessible to
observation through an endoscope passed through the mouth.
Fluoroscopy: Examination of deep structures by means of an X-ray
fluoroscope.
GI (Gastrointestinal): Pertaining to the stomach and intestine.
Proctoscopy: Inspection of the rectum with a proctoscope.
Sigmoidoscopy: A rigid or flexible illuminated endoscope for
examination of the sigmoid (shaped like the letter 'S' or the letter
'C') colon.
1.3.3.1 Notes on Indoor Design Conditions:
(a) These are design conditions and not operating limits. All
thermostats shall be adjustable between 15 to 29 degrees C (60 to 85
degrees F).
not be maintained by any humidity control either at the air terminal
units or at the air-handling units. These values merely represent the
design reference points and, in actual practice, would vary due to the
predetermined air quantities and fluctuations in the internal heat
Table 1-1 shall be maintained by a humidity control either at the air
terminal units, or at the air handling unit or both.
HVAC DESIGN MANUAL
1-6
GENERAL REQUIREMENTS