lead or 0.45 kg (16 ounce) soft copper membrane, 600 mm (24
inches) square.
6.
PIPE BASEMENTS
6.1
Evaluate the use of full or partial pipe basements on an
that a pipe basement is the most efficient and economical method
of adapting piping, duct, and electrical conduit systems to the
building. Design pipe basements to provide a minimum clearance of
1200 mm (4'-0") under pipes, ducts, and electrical conduits for
access to these systems for maintenance and repair. Locate all
areas of a pipe basement between two means of emergency exits.
Extend stairways down to the pipe basement by means of industrial
stairs.
7