Draft 7-6-95
Design Standards
Radiology - General Purpose Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
--
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
--
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. 4'-0" lead lined entry door
Relative Humidity/Cooling:
50%
2. Lead lined partitions
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
4
SPECIAL EQUIPMENT
Room Pressure:
0
AC Load-Equipment:
5.0 w/sft (see note 1)
None
AC Load Lighting:
2.6 w/sft
LIGHTING
Number of People:
2
--
General:
--
Notes: 1. Check with the equipment
Special:
--
Notes:
into the room.
POWER
PLUMBING AND MEDICAL GASES
General:
--
Emergency:
--
Cold Water:
Yes
Notes:
--
Hot Water:
Yes
Laboratory Air:
--
COMMUNICATION
Laboratory Vacuum:
--
Sanitary Drain:
Yes
ADP:
--
Reagent Grade Water:
--
Radio:
--
Medical Air:
--
Telephone:
--
Medical Vacuum:
--
Intercom:
--
Oxygen:
--
Pub. Addr:
--
Notes:
Notes:
VA Design Guide
PAGE 6 - 4
Community Based Outpatient Clinic