Draft 7-6-95
Design Standards
Radiology - Film Processing Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Painted GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
100%
Base:
4" Resilient Base
Yes
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
8
Room Pressure:
Negative
None
AC Load-Equipment:
(7.5w/sf)
LIGHTING
AC Load-Lighting:
(1.6w/sf)
Number of People:
1
General:
--
Special Exhaust:
--
Special:
--
Notes:
Notes:
4" round duct with lead shielding
POWER
for film processing.
2. Maintain negative pressure by
General:
--
exhausting 15% more air than
Emergency:
--
supply air.
Notes:
--
COMMUNICATION
PLUMBING AND MEDICAL GASES
ADP:
--
Cold Water:
Yes
Radio:
--
Hot Water:
Yes
Telephone:
--
Laboratory Air:
--
Intercom:
--
Laboratory Vacuum:
--
Pub. Addr:
--
Sanitary Drain:
Yes
Notes:
Reagent Grade Water:
--
Medical Air:
--
Medical Vacuum:
--
Oxygen:
--
Notes:
1. Chemical resistant pipe for
sanitary.
VA Design Guide
PAGE 6 - 5
Community Based Outpatient Clinic