Draft 7-6-95
Design Standards
Pharmacy - Expanded Service
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
22C (72F)
Wall Finish:
GWB (see note 1)
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. Perimeter wall full height 6"
Relative Humidity/Cooling:
50%
CMU-P.
Relative Humidity/Heating:
30%
2. Perimeter barricade wall special
Minimum Air Changes/Hr.:
4
locks, entry doors
Room Pressure:
0
AC Load-Equipment:
(5.1w/sf)
SPECIAL EQUIPMENT
AC Load-Lighting:
(2.4w/sf)
Number of People:
2
None
--
LIGHTING
Notes:
--
General:
2x4 flour
PLUMBING AND MEDICAL GASES
Special:
--
Cold Water:
--
Notes:
Hot Water:
--
POWER
Laboratory Air:
--
Laboratory Vacuum:
--
General:
--
Sanitary Drain:
--
Emergency:
--
Reagent Grade Water:
--
Notes:
--
Medical Air:
--
COMMUNICATION
Medical Vacuum:
--
Oxygen:
--
ADP:
--
Notes:
Radio:
--
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
PAGE 6 - 3
Community Based Outpatient Clinic