Draft 7-6-95
Design Standards
Clean Utility Room
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base
Yes
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. 4'-0" Door
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
Positive
None
AC Load-Equipment:
2.0 w/sf
LIGHTING
AC Load-Lighting:
4.5 w/sf
Number of People:
2
General:
30FC - 1.5 W/SF
--
Special:
--
Notes:
--
Notes:
POWER
PLUMBING AND MEDICAL GASES
General:
180 w
Cold Water:
Yes
Emergency:
--
Hot Water:
Yes
Notes:
--
Laboratory Air:
--
Laboratory Vacuum:
--
COMMUNICATION
Sanitary Drain:
Yes
Reagent Grade Water:
--
ADP:
--
Medical Air:
--
Radio:
--
Medical Vacuum:
--
Telephone:
--
Oxygen:
--
Intercom:
--
Notes:
Pub. Addr:
--
Notes:
VA Design Guide
PAGE 5 - 9
Community Based Outpatient Clinic