Draft 7-6-95
Design Standards
Soiled Utility Room
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB (see note 1)
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15%
Base:
4" Resilient Base (see note 2)
--
Floor Finish:
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. CT full height on fixture wall
Relative Humidity/Cooling:
50%
2. RB on three (3) walls
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
6
SPECIAL EQUIPMENT
Room Pressure:
Negative
AC Load-Equipment:
(3.3 w/sf)
AC Load-Lighting:
(2.5w/sf)
None
Number of People:
1
LIGHTING
--
Notes:
--
General:
(30fc)
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
Cold Water:
Yes
POWER
Hot Water:
Yes
Laboratory Air:
--
General:
180 w
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
--
Reagent Grade Water:
--
COMMUNICATION
Medical Air:
--
Medical Vacuum:
--
ADP:
--
Oxygen:
--
Radio:
--
Notes:
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
PAGE 5 - 10
Community Based Outpatient Clinic