Draft 7-6-95
Design Standards
Patient Wheelchair Toilet
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2400 mm (8'-0")(see note 1)
Dry Bulb Temp Cooling:
--
Wall Finish:
CT
22C (72F)
Wainscot:
--
Minimum % Outside Air:
100%
Base:
CT
Yes
Floor Finish:
CT
Noise Criteria:
NC-40
Sound Protection:
Yes (see note 2)
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
--
Notes: 1. Perimeter partitions full height
Relative Humidity/Heating:
--
Minimum Air Changes/Hr.:
10
Room Pressure:
Negative
SPECIAL EQUIPMENT
AC Load-Equipment:
--
AC Load-Lighting:
--
None
Number of People:
--
LIGHTING
--
Notes:
--
General:
30FC - 1.5 W/SF
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
Cold Water:
Yes
POWER
Hot Water:
Yes
Laboratory Air:
--
General:
180 W
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
--
Reagent Grade Water:
--
COMMUNICATION
Medical Air:
--
Medical Vacuum:
--
ADP:
--
Oxygen:
--
Radio:
--
Notes:
Telephone:
--
Intercom:
--
Pub. Addr:
--
Nurse Call:
Yes
Notes:
VA Design Guide
PAGE 5 - 8
Community Based Outpatient Clinic