Draft 7-6-95
Design Standards
Multipurpose Procedure Room
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
2895 mm (9'-6") (see note 1)
Dry Bulb Temp Cooling:
24C (76F)
Wall Finish:
GWB
25C (78F)
Wainscot:
--
Minimum % Outside Air:
100%
Base:
4" Resilient Base
Yes
Floor Finish:
Noise Criteria:
NC-40
Sound Protection:
Yes (see note 2)
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. Perimeter partitions full height
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
8
3. Bulletin Board
Room Pressure:
Negative
AC Load-Equipment:
8.0 W/SF
SPECIAL EQUIPMENT
AC Load-Lighting:
2.7 W/SF
Number of People:
5
None
--
LIGHTING
Notes:
--
General:
50-100FC (see note 1)
PLUMBING AND MEDICAL GASES
Special:
--
Cold Water:
Yes
Notes:
1. 2.5-5.0 W/SF, Fluor lamp of
Hot Water:
Yes
deluxe color improved type.
Laboratory Air:
--
2. 18" DIA portable examination
Laboratory Vacuum:
--
light, 120V.
Sanitary Drain:
Yes
POWER
Reagent Grade Water:
--
Medical Air:
--
General:
1200 W
Medical Vacuum:
--
Emergency:
--
Oxygen:
--
Notes:
--
Notes:
COMMUNICATION
ADP:
Empty Conduit
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA Design Guide
PAGE 5 - 7
Community Based Outpatient Clinic