Final Draft 10-18-96
Revised February 1997
Design Standards
Soiled Utility Room
ARCHITECTURAL
CONDITIONING
Ceiling:
SC Gwbd
Ceiling Ht:
400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
SC Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
--
Base:
Resilient Base
Yes
Floor Finish:
Ceramic Tile
Noise Criteria:
40
Slab Depr:
--
Steam:
--
Notes:
1. Full height ceramic tile - 3 walls
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
6
Room Pressure:
Negative
None
2
AC Load-Equipment:
38W/m (3.5W/SF)
38W/m 2 (3.5W/SF)
AC Load Lighting:
LIGHTING
Number of People:
--
General:
30FC
--
Special:
--
Notes:
1. See HVAC Design Manual for
Notes:
1. 600 mmx1200 mm (2'x4')
Hospital Projects for other
considerations.
fixture, acrylic prismatic lens,
W/2-F32T8 lamps, 3500oK,
PLUMBING AND MEDICAL GASES
CRI=75
(Minimum)
Cold Water:
Yes
POWER
Hot Water:
Yes
Laboratory Air:
--
General:
180 w
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
Yes
Notes:
--
Reagent Grade Water:
--
Medical Air:
--
COMMUNICATION
Medical Vacuum:
--
ADP:
--
Oxygen:
--
Radio:
--
Notes:
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY
PAGE 5-6