Final Draft 10-18-96
Revised February 1997
Design Standards
Housekeeping Aids Closet
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Ceiling Ht:
400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
GWB SC Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
--
Base:
Welded Seamless Flooring
Yes
Floor Finish:
Welded Seamless Flooring
Noise Criteria:
40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
10
Room Pressure:
Negative
None
2
AC Load-Equipment:
20W/m (1.8W/SF)
27W/m 2 (2.5W/SF)
AC Load Lighting:
LIGHTING
Number of People:
--
General:
30FC
--
Special:
--
Notes:
--
Notes:
PLUMBING AND MEDICAL GASES
fluorescent light fixture, acrylic prismatic
o
Cold Water:
Yes
lens, W/2-F32T8 lamps, 3500 K,
Hot Water:
Yes
CRI = 75 (Minimum)
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
Yes
General:
180 w
Reagent Grade Water:
--
Emergency:
--
Medical Air:
--
Notes:
--
Medical Vacuum:
--
Oxygen:
--
COMMUNICATION
Notes:
ADP:
--
Radio:
--
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY