Final Draft 10-18-96
Revised February 1997
Design Standards
Clean Utility Room
ARCHITECTURAL
CONDITIONING
Ceiling:
SC Gwbd
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient Base
Yes
Floor Finish:
Noise Criteria:
40
Slab Depr:
--
Steam:
--
Notes:
1. 1200 mm (4'-0") Wide door
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
Positive
None
2
AC Load-Equipment:
27W/m (2.5W/SF)
38W/m 2 (3.5W/SF)
AC Load Lighting:
LIGHTING
Number of People:
2
General:
30FC
--
Special:
--
Notes:
Notes:
1. 600mm x 1200mm (2' x 4')
1. See HVAC Design Manual for
Hospital Projects for other
fixture, acrylic prismatic lens,
considerations .
with 2-F32T8 lamps, 3500 deg.
K, CRI=75 (minimum).
PLUMBING AND MEDICAL GASES
Cold Water:
Yes
POWER
Hot Water:
Yes
General:
80 w
Laboratory Air:
--
Emergency:
--
Laboratory Vacuum:
--
Notes:
--
Sanitary Drain:
Yes
Reagent Grade Water:
--
COMMUNICATION
Medical Air:
--
ADP:
--
Medical Vacuum:
--
Radio:
--
Oxygen:
--
Telephone:
Yes
Notes:
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY
PAGE 5-5