Final Draft 10-18-96
Revised February 1997
Design Standards
Anesthesia Workroom & Equipment Storage
ARCHITECTURAL
CONDITIONING
Ceiling:
Gwbd.
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Gwbd Paint (Special Coat)
22C (72F)
Wainscot:
--
Minimum % Outside Air:
---
Base:
Resilient Base
Yes
Floor Finish:
Noise Criteria:
40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
--
Room Pressure
Negative
None
2
AC Load-Equipment:
32W/m (3W/SF)
32W/m 2(3W/SF)
AC Load Lighting:
LIGHTING
Number of People:
3
General:
30FC
--
Special:
--
Notes: --
1. 600 mm x 1200 mm (2'x4')
Notes:
PLUMBING AND MEDICAL GASES
fixture, acrylic prismatic lens,
Cold Water:
Yes
W/2-F32T8 lamps, 35000K,
Hot Water:
Yes
CRI=75 (Min.)
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
Yes
General:
--
Reagent Grade Water:
--
Emergency:
--
Medical Air:
Yes
Notes:
--
Medical Vacuum:
Yes
Oxygen:
Yes
COMMUNICATION
Notes:
ADP:
--
Radio:
--
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY
PAGE 5-4