Design Standards
Changing Cubicles & Patient Lockers
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
---
Base:
Resilient Base
Yes
Floor Finish:
Noise Criteria:
40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
Negative
None
2
AC Load-Equipment:
1W/m (1W/SF)
22W/m 2 (2W/SF)
AC Load Lighting:
LIGHTING
Number of People:
2
General:
30FC
--
Special:
--
Notes:
--
Notes:
PLUMBING AND MEDICAL GASES
fluorescent light fixture, acrylic
Cold Water:
--
prismatic lens.
Hot Water:
--
Laboratory Air:
--
fluorescent light fixture, acrylic
Laboratory Vacuum:
--
prismatic lens.
Sanitary Drain:
--
3. Provide nurse call light in corridor.
Reagent Grade Water:
--
Medical Air:
--
Medical Vacuum:
--
POWER
Oxygen:
--
General:
--
Notes:
Emergency:
--
Notes:
--
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY
PAGE 5-3