Final Draft 10-18-96
Revised February 1997
Design Standards
Consultation Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15% (Note 1)
Base:
Resilient Base
Noise Criteria:
40
Floor Finish:
Carpet
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
1. Provide STC 40 PTNS & Door
Relative Humidity/Heating:
30%
2. 3'-0" Wide Door
Minimum Air Changes/Hr.:
4
Room Pressure:
Equal
2
SPECIAL EQUIPMENT
AC Load-Equipment:
43W/m (4W/SF)
32W/m 2 (3W/SF)
AC Load Lighting:
None
Number of People:
3
--
LIGHTING
Notes:
General:
30FC
1. See HVAC Design Manual for Hospital
Special:
--
Projects for other considerations.
Notes:
1. 600mm x 1200mm (2' x 4')
PLUMBING AND MEDICAL GASES
Cold Water:
--
acrylic prismatic lens, with 2-
Hot Water:
--
F32T8 lamps, 3500 deg. K,
Laboratory Air:
--
CRI=75 (minimum).
Laboratory Vacuum:
--
Sanitary Drain:
--
POWER
Reagent Grade Water:
--
General:
--
Medical Air:
--
Emergency:
--
Medical Vacuum:
--
Notes:
--
Oxygen:
--
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY
PAGE 5-2