Final Draft 10-18-96
Revised February 1997
Design Standards
Nurse Station
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2400 mm (8'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15 (Note 1)
Base:
Resilient Base
Yes
Floor Finish:
Carpet
Noise Criteria:
40
Slab Depr:
--
Steam:
--
Notes:
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
6
Room Pressure:
Equal
None
AC Load-Equipment:
54W/m 2 (5W/SF)
AC Load Lighting:
64W/m 2 (6W/SF)
LIGHTING
Number of People:
5
General:
70FC
--
Special:
Notes:
Notes:
1. 600 mm x 1200 mm (2'x4')
1. See HVAC Design Manual for
Hospital Projects for other
acryliclens,w/2-F32T8 lamps,
cosiderations.
3500 deg. K, CRI=75 (Min.)
PLUMBING AND MEDICAL GASES
dimmer.
Cold Water:
--
Hot Water:
--
POWER
Laboratory Air:
--
General:
--
Laboratory Vacuum:
--
Emergency:
--
Sanitary Drain:
--
Notes:
--
Reagent Grade Water:
--
Medical Air:
--
COMMUNICATION
Medical Vacuum:
--
ADP:
Yes
Oxygen:
--
Radio:
--
Notes:
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY SURGERY
PAGE 5-1