FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Chemotherapy Agent Preparation Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Veneer plaster, paint
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Veneer plaster, paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
--
Base:
Resilient sheet flooring integral
Yes
base
Noise Criteria:
NC-40
Floor Finish: Resilient sheet flooring
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
60%
Notes:
1. 900 mm (3'-0") wide door.
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
12
SPECIAL EQUIPMENT
Room Pressure:
Prep area is Positive
Ante is Negative with
None
respect to adjacent
LIGHTING
areas.
16 W/m 2(1.5 W/sf)
AC Load Lighting:
General:
50 FC
2
AC Load-Equipment:
54 W/m (5 W/sf)
Special:
--
Number of People:
6
Notes:
1. 600 mm x 1200 mm (2'x4')
Biological safety cabinet
exhaust.See HVAC
fixture, acrylic prismatic lens,
Design Manual for
W/3-F32T8 lamps, 4100K,
Hospital Projects.
CRI=85 (minimum).
Notes:
POWER
PLUMBING AND MEDICAL GASES
General:
Cold Water:
Yes
Emergency:
--
Hot Water:
Yes
Notes:
1. Junction box for 120V critical
Laboratory Air:
Yes
power connection to
Laboratory Vacuum:
Yes
refrigerator.
Sanitary Drain:
Chemical-resist. type.
2. Junction box for 120V power
Reagent Grade Water:
--
Medical Air:
--
cabinet.
Medical Vacuum:
--
Oxygen:
--
COMMUNICATION
Notes:
1. Provide one natural gas outlet.
ADP:
--
2. All outlets need to be on the left
Radio:
--
Telephone:
Yes
cabinet.
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-15