FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Chemotherapy Treatment Room
ARCHITECTURAL
CONDITIONING
Ceiling:
with washable finish
Dry Bulb Temp Cooling:
24C (76F)
Ceiling Ht:
2700 mm (9'-0")
25C (78F)
Wall Finish:
Veneer plaster, paint
Minimum % Outside Air:
--
Wainscot:
--
Yes
Base:
Resilient sheet flooring integral
Noise Criteria:
NC-35
base
Steam:
--
Floor Finish: Resilient sheet flooring
Relative Humidity/Cooling:
50%
Slab Depr:
--
Relative Humidity/Heating:
30%
Notes:
1. 1220 mm (3'-8") wide door.
Minimum Air Changes/Hr.:
8
Room Pressure:
Negative
2
SPECIAL EQUIPMENT
AC Load Lighting:
16 W/m (1.5 W/sf)
65 W/m 2 (6 W/sf)
AC Load-Equipment:
None
Number of People:
10
LIGHTING
Yes
0
Notes:
Provide capability to maintain 29 C
General:
30 FC
0
(85 F) year round.
Special:
---
Notes:
1. Cubicles have individual
PLUMBING AND MEDICAL GASES
switches for separate control of
Cold Water:
Yes
up/down lights.
Hot Water:
Yes
2. 600 mm x 600 mm (2'x2')
Laboratory Air:
--
Laboratory Vacuum:
--
fixture, acrylic prismatic lens,
Sanitary Drain:
Yes
W/2-FB31 lamps, 3500K,
Reagent Grade Water:
--
CRI=75 (minimum).
Medical Air:
Yes
3. Wall-mounted fluorescent
Medical Vacuum:
Yes
direct/indirect fixture, acrylic
Oxygen:
Yes
prismatic lens, W/4-F32T8
Notes:
lamps, 2-up and 2-down,
separately ballasted.
POWER
General:
Emergency:
--
Notes:
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
--
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-14