FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Orthopedic Clinic/Cast Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Veneer plaster, paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
--
Base:
Resilient sheet flooring integral
Yes
base
Noise Criteria:
NC-40
Floor Finish: Resilient sheet flooring
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
1. 1200 mm (4'-0") wide door.
Relative Humidity/Heating:
30%
Minimum Air Changes/Hr.:
10
SPECIAL EQUIPMENT
Room Pressure
Negative
2
AC Load Lighting:
26 W/m (2.4 W/sf)
None
54 W/m 2 (5 W/sf)
AC Load-Equipment:
LIGHTING
Number of People:
4
Yes
General:
Cubicle: 100 FC
Notes:
Work Area: 50 FC
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
1. Local switching by area/cubicle.
2. 600 mm x 1200 mm (2'x4')
Cold Water:
Yes
Hot Water:
Yes
fixture, acrylic prismatic lens,
Laboratory Air:
--
W/4-F32T8 lamps, 3500K,
Laboratory Vacuum:
--
Sanitary Drain:
Yes
CRI=75 (minimum).
Reagent Grade Water:
--
3. 600 mm x 1200 mm (2'x4')
Medical Air:
Yes
Medical Vacuum:
Yes
fixture, acrylic prismatic lens,
W/2-F32T8 lamps, 3500K,
Oxygen:
--
Notes:
CRI=75 (minimum).
POWER
General:
Emergency:
--
Notes:
COMMUNICATION
ADP:
--
Radio;
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-13