FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. 900 mm (3'-0") wide doors
Relative Humidity/Cooling:
50%
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
4
Room Pressure:
0
None
2
AC Load Lighting:
78 W/m (7 W/sf)
32 W/ m 2 (3 W/sf)
AC Load-Equipment:
LIGHTING
Number of People:
1
General:
30 FC
--
Special:
--
Notes:
Notes:
1. 600 mm x 1200 mm (2'x4')
PLUMBING AND MEDICAL GASES
fixture, acrylic prismatic lens,
W/2-F32T8 lamps, 3500K,
Cold Water:
Yes
Hot Water:
Yes
CRI=75 (Minimum)
Laboratory Air:
--
Laboratory Vacuum:
--
POWER
Sanitary Drain:
Yes
General:
Reagent Grade Water:
--
Emergency:
--
Medical Air:
--
Notes:
Medical Vacuum:
--
Oxygen:
--
COMMUNICATION
Notes:
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-11