FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Dermatology Procedure Treatment Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Ceiling Ht:
2700 mm (9'-0")
Dry Bulb Temp Cooling:
25C (78F)
Wall Finish:
Paint
22C (72F)
Wainscot:
--
Minimum % Outside Air:
15
Base:
Resilient base
--
Noise Criteria:
NC-40
Slab Depr:
--
Steam:
--
Notes:
1. Provide STC 40 partitions and
Relative Humidity/Cooling:
50%
door.
Relative Humidity/Heating:
30%
2. 900 mm (3'-0") wide door.
Minimum Air Changes/Hr.:
8
Room Pressure:
0
2
SPECIAL EQUIPMENT
AC Load Lighting:
19 W/m (1.8 W/sf)
65 W/m 2 (6 W/sf)
AC Load-Equipment:
None
Number of People:
3
--
LIGHTING
Notes:
General:
100 FC
Special:
--
PLUMBING AND MEDICAL GASES
Notes:
1. 50% of lighting on critical
power.
Cold Water:
Yes
2. 600 mm x 1200 mm (2'x4')
Hot Water:
Yes
Laboratory Air:
--
fixture, acrylic prismatic lens
Laboratory Vacuum:
--
W/4-F32T8 lamps, 3500K,
Sanitary Drain:
Yes
Reagent Grade Water:
--
CRI=75 (minimum).
Medical Air:
--
Medical Vacuum:
--
POWER
Oxygen:
--
General:
Notes:
(dedicated receptacle/circuit for
electrocautery unit).
Emergency:
200W (receptacle)
Notes:
1. Junction box for 120V power
connection to surgical light.
ADP:
--
Radio: --
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
1. Nurse call
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-10