FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Gastroenterology Procedure Treatment Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum wallboard lay-in ceiling
panel
Dry Bulb Temp Cooling:
22C (72F)
Ceiling Ht:
2700 mm (9'-0")
25C (78F)
Wall Finish:
Paint
Minimum % Outside Air:
--
Wainscot:
--
Yes
Base:
Resilient sheet flooring integral
Noise Criteria:
NC-40
base
Steam:
--
Floor Finish: Resilient sheet flooring
Relative Humidity/Cooling:
50%
Slab Depr:
--
Relative Humidity/Heating:
30%
Notes:
1. Provide STC 40 partitions and
Minimum Air Changes/Hr.:
8
door
Room Pressure:
Negative
2
2. 900 mm (3'-0") wide door.
AC Load Lighting:
19 W/m (1.8 W/sf)
65 W/m 2 (6W/sf)
AC Load-Equipment:
SPECIAL EQUIPMENT
Number of People:
3
--
None
Notes:
LIGHTING
PLUMBING AND MEDICAL GASES
General: 50 FC ambient/100 FC task
Special:
--
Cold Water:
Yes
Notes:
1. 50% of lights on critical power
Hot Water:
Yes
2. 600 mm x 1200 mm (2'x4')
Laboratory Air:
--
Laboratory Vacuum:
--
fixture, acrylic prismatic lens,
Sanitary Drain:
Yes
W/4-F32T8 lamps, 3500K,
Reagent Grade Water:
--
Medical Air:
--
CRI=75 (Minimum)
Medical Vacuum:
--
Oxygen:
--
POWER
Notes:
General:
2.1000W (dedicated circuit for
exam table.
Emergency:
Notes:
--
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
1. Nurse call
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-7