FINAL DRAFT 10-31-95
REVISED January 1997
Design Standards
Intake/Exit Interview Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Gypsum wallboard lay-in ceiling
panel
Dry Bulb Temp Cooling:
25C (78F)
Ceiling Ht:
2700 mm (9'-0")
22C (72F)
Wall Finish:
Paint
Minimum % Outside Air:
15
Wainscot:
--
--
Base:
Resilient base
Noise Criteria:
NC-40
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
1. Provide STC 40 partitions and
Relative Humidity/Heating:
30%
door.
Minimum Air Changes/Hr.:
4
2. 900 mm (3'-0") wide door.
Room Pressure:
0
2
AC Load Lighting:
15 W/m (1.4 W/sf)
65 W/m 2 (6 W/sf)
SPECIAL EQUIPMENT
AC Load-Equipment:
Number of People:
3
None
--
Notes:
LIGHTING
General:
50 FC (Ambient)
PLUMBING AND MEDICAL GASES
Special:
--
Notes:
1. 600 mm x 1200 mm (2'x4')
Cold Water:
--
Hot Water:
--
fixture, acrylic prismatic lens,
Laboratory Air:
--
W/2-F32T8 lamps, 3500K,
Laboratory Vacuum:
--
Sanitary Drain:
--
CRI=75 (Minimum)
Reagent Grade Water:
--
Medical Air:
--
POWER
Medical Vacuum:
--
General:
Oxygen:
--
Emergency:
--
Notes:
Notes:
COMMUNICATION
ADP:
Yes
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
VA DESIGN GUIDE
AMBULATORY CARE (Hospital Based)
PAGE 6-6