A/E CHECKLIST
TITLE________________________________PROJECT NO. ______________
LOCATION___________________________________DATE ______________
REVIEWED BY ___________________________________________________
ORGANIZATION _________________________________________________
LIFE SAFETY ISSUES
A
SMOKE AND FIRE PROTECTION
(cont.)
13
Per NFPA 90A, the following hazardous exhaust ducts shall not be
Para. 2.11.2.2
housed in the same shaft carrying environmental supply, return or
exhaust ducts:
Exhaust from fume hoods, ETO sterilizers, kitchen grease laden hoods
ortho/prosthetic lab, and battery charging rooms.
14
Per NFPA 30, provide a dedicated exhaust system for each flammable
Para. 4.5
and combustible liquid storage space. Provide an explosion proof
motor and spark proof fan, and flow monitoring and alarm system.
Para. 3.12 and
VA Master
15
Conform kitchen hood exhaust to NFPA 96.
Spec Section
15250.
Para. 2.16
B
EMERGENCY POWER
1
Where outdoor winter design temperature is -6.5 degrees C (20 degrees
F) or less, provide building heating equipment on emergency power as
"
required by NFPA 99.
2
Exhaust fans serving labs, emergency generator rooms, ETO exhaust,
"
Xenon and Iodine gases, battery charging rooms, flammable storage
rooms, Atrium smoke control, and HVAC equipment serving critical
areas of OPCs in seismic and high risk hurricane areas etc.
Para. 3.19
C
LEAD LINING OF DUCT WORK
Provide lead lining on ductwork penetrating lead lined walls.
"
Application
D
SPECIAL VENTILATION
4.12
Radioactive Xenon gas and iodine require special exhaust system.
"
5