June 2006
A/E CHECKLIST
TITLE________________________________PROJECT NO. ______________
LOCATION___________________________________DATE ______________
REVIEWED BY ___________________________________________________
ORGANIZATION _________________________________________________
LIFE SAFETY ISSUES
REVIEW
A
SMOKE AND FIRE PROTECTION
(cont.)
7
See smoke control flow diagram for air handling units. Note
Para 2.13.4 and
requirements for unit sizes exceeding 56 m3 /min (2,000 CFM) and 420
Para. 2.13.2
m3 / min (15,000 CFM).
Unit > 56 m3 / min (2,000 CFM): Provide a smoke detector in main
supply duct
Unit > 420 m3 / min (15,000 CFM), and the system serves more
than one story: Provide a smoke detector in each return branch at
each floor in addition to a detector in supply main; Isolate unit by
providing smoke dampers in the supply and return air ducts only if
it serves more than one floor.
8
Show control diagrams for control of smoke dampers with smoke
VA Standard
Detail 15902 -
34 DWG
9
No duct mounted smoke detectors or smoke dampers required when
Para. 2 .13.2.5
crossing a smoke barrier in a fully sprinkled building with quick
response sprinklers,
10
"
11
NFPA 45 does not permit fire dampers in Laboratory fume hood
Para. 2.13.3.3
exhaust. Provide a separate fire rated shaft from each fire zone to reach
top of the building.
12
Provide smoke venting for elevator shafts. When standby power is
VA Standard
connected to an elevator, NFPA 101 requires the machine room
Detail 15902
ventilation/air conditioning system also to be connected to standby
32 DWG
power.
4