May 2006
A/E CHECKLIST
TITLE________________________________PROJECT NO. ______________
LOCATION___________________________________DATE ______________
REVIEWED BY ___________________________________________________
ORGANIZATION _________________________________________________
DESIGN DEVELOPMENT
ELECTRICAL REVIEW
COMMENTS/
NO.
ITEM
YES/NO/NA
4
Miscellaneous Alarms as indicated in Design and Construction
Procedures 801-7 (See Electrical Design Manual), such as Blood Bank
refrigeration, Medical Gas System Alarm and others.
5
Electrical sub-metering equipment for boiler plants, energy buildings,
laundry buildings, and new separate buildings as required in chapter of
the VA Electrical Design Manual.
6
Remote Dictating System: Dial-Link or Direct-wired. (See Electrical
Design Manual) for new hospitals and laboratory service areas.
7
Lightning Protection System. (See Electrical Design Manual). Use the
Risk Assessment Guide, Appendix H of the NFPA 780 to determine
the requirement.
8
Fire Alarm Systems: Local building systems and base Loop Systems
(See Electrical Design Manual) and Engineering Guide For Fire
Protection Design Manual by Division 10NB:
a. Location of alarm devices and indicating devices.
b. Number of alarm devices and indicating devices.
c. Zoning coordination with Plumbing, Mechanical and
Architectural services.
d. Other system components such as building code transmitters,
annunciators, batteries, charges etc.
9
Coordinate drawings with other technical disciplines
10
Compliance with VA National CAD Standard Application Guide and
applicable National CAD Standard modules.
7