May 2006
A/E CHECKLIST
TITLE________________________________PROJECT NO. ______________
LOCATION___________________________________DATE ______________
REVIEWED BY ___________________________________________________
ORGANIZATION _________________________________________________
DESIGN DEVELOPMENT
ELECTRICAL REVIEW
COMMENTS/
NO.
ITEM
YES/NO/NA
1
All electrical rooms, transformer vaults and closets shall not be located
directly below showers, laboratories, kitchens, dishwashing areas or
other areas where water service is provided. Pipe containing liquids or
gases shall not pass through these rooms.
2
Compliance To Design and Construction Procedures/ NEC/...
a. Requirements for Essential Electrical system distribution follow
NEC 517-30/517-40 and Essential Electrical Design Manual.
b. Requirements for Primary and Secondary transformation and
distribution equipment are followed as Design and Construction
Procedures (See Electrical Design Manual).
c. Receptacles, mounting heights as required in different areas (See
Electrical Design Manual)
d. Raceways required in Fluoroscopic, Radiographic and Deep
Therapy rooms. (See Electrical Design Manual).
e. Raceway systems as required in Design and Construction
Procedures 801-5 (See Electrical Design Manual).
(1) All wiring shall be installed in raceways.
(2) Underground raceways shall be encased in concrete.
(3) Isolated power systems wiring installed in plastic coated
conduits.
3
Alarms: Nonflammable medical gas and medical- surgical vacuum
systems. (See Electrical Design Manual) and NFPA 99:
a. Master alarm panels required at the telephone switchboard and
engineering control center or boiler plant.
b. Area alarms provided at nurses stations where medical gas
systems are installed.
6