First Draft 3-15-97
Design Standards
Radiographic Film Processing Room
ARCHITECTURAL
CONDITIONING
Ceiling:
GWB
Dry Bulb Temp Cooling:
25C (78F)
Ceiling Ht:
2700 MM (9'-0")
22C (72F)
Wall Finish:
Paint (SC)
Minimum % Outside Air:
100
Wainscot:
--
Yes
Base:
Welded Seamless Flooring
Noise Criteria:
NC-40
Floor Finish:
Welded Seamless Flooring
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
--
Relative Humidity/Heating:
30%
SPECIAL EQUIPMENT
Minimum Air Changes/Hr.:
8 (SA)
None
Room Pressure:
Negative
AC Load Lighting:
None
LIGHTING
AC Load-Equipment:
81 w/sm (7.5 w/sf)
General:
0 -10 FC (incandescent)
Number of People:
3
Special:
Safety Light
Yes (see note 1)
Notes:
--
Notes:
1. 4" round duct for film processor.
Ducts require lead shielding.
POWER
PLUMBING AND MEDICAL GASES
General:
180W
Cold Water:
Yes
Emergency:
--
Hot Water:
Yes
Notes:
--
Acid Waste:
Yes
COMMUNICATION
Silver Recovery:
Yes
ADP:
--
Laboratory Air:
--
Radio:
--
Laboratory Vacuum:
--
Telephone:
--
Sanitary Drain:
Yes
Intercom:
--
Reagent Grade Water:
--
Pub. Addr:
--
Medical Air:
--
Notes:
--
Medical Vacuum:
--
Oxygen:
--
Notes:
--
VA DESIGN GUIDE
AMBULATORY CARE INVASIVE PROCEDURES SUITE
PAGE 5-6