First Draft 3-15-97
Design Standards
Scope Cleaning / Clean Storage
ARCHITECTURAL
CONDITIONING
Ceiling:
Acoustical ceiling tile
Dry Bulb Temp Cooling:
25C (78F)
Ceiling Ht:
2700 MM (9'-0")
22C (72F)
Wall Finish:
High build glazed coating
Minimum % Outside Air:
--
Wainscot:
--
Yes
Base:
Welded Seamless Flooring
Noise Criteria:
NC-40
Floor Finish:
Welded Seamless Flooring
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes: 1. 900mm (3'-0") wide entry doors
Relative Humidity/Heating:
30%
with tempered glass view window.
Minimum Air Changes/Hr.: Scope Cleaning: 10
SPECIAL EQUIPMENT
Clean Storage: 4
None
Room Pressure:
Scope Cleaning: Negative
Clean Storage: Positive
LIGHTING
AC Load Lighting:
General:
30 FC
Scope Cleaning: 54 w/sm (5 w/sf)
Special:
--
Clean Storage: 22 w/sm (2 w/sf)
Notes:
1. 600mm x 1200mm (2'x4')
AC Load-Equipment:
Scope Cleaning: 13 w/sm (1.2 w/sf)
fixture, acrylic prismatic lens,
Clean Storage: 19 w/sm (1.8 w/sf)
W/2-F32T8 lamps, 3500K,
Number of People:
2
Special Exhaust:
--
CRI=75 (Min.).
Notes:
POWER
scope cleaning room.
General:
PLUMBING AND MEDICAL GASES
Emergency:
--
Cold Water:
Yes
Notes:
1. Special receptacle for
Hot Water:
Yes
endoscopy washer, (coordinate
Laboratory Air:
--
with supplier)
Laboratory Vacuum:
--
COMMUNICATION
Sanitary Drain:
Yes
Reagent Grade Water:
--
ADP:
--
Medical Air:
Yes
Radio:
--
Medical Vacuum:
Yes
Telephone:
Yes
Oxygen:
Yes
Intercom:
--
Notes:
1. Sink, drain pipe, waste and vent
Pub. Addr:
--
from the sink located in the
Notes:
--
scope cleaning room needs to
be chemical resistant type.
VA DESIGN GUIDE
AMBULATORY CARE INVASIVE PROCEDURES SUITE
PAGE 5-7