First Draft 3-15-97
Design Standards
Proctoscopy / Sigmoidoscopy Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Dry Bulb Temp Cooling:
25C (78F)
Gyp. Wall Bd. In Toilet Rm.
22C (72F)
Ceiling Ht:
2700 mm (9'-0")
Minimum % Outside Air:
--
Wall Finish:
Paint
Yes
Ceramic Tile in Toilet Room
Noise Criteria:
NC-40
Wainscot:
--
Steam:
--
Base: Resilient sheet flooring w/ integral base
Relative Humidity/Cooling:
50%
Floor Finish:
Resilient sheet flooring
Relative Humidity/Heating:
30%
Ceramic Tile in Toilet Room
Minimum Air Changes/Hr.:
6
Slab Depr:
--
Room Pressure:
Negative
Notes: 1. 900mm (3'-0") wide entry door.
AC Load Lighting:
30 w/sm (2.8 w/sf)
SPECIAL EQUIPMENT
AC Load-Equipment:
54 w/sm (5 w/sf)
None
Number of People:
4
--
LIGHTING
Notes:
General:
Procto Rm :100 FC
PLUMBING AND MEDICAL GASES
Toilet: 30 FC
Cold Water:
Yes
Special:
--
Hot Water:
Yes
Notes: 1. Lighting control by area;
Laboratory Air:
--
switch(es) at room entrance.
2. 600mm x 1200mm (2' x 4')
Laboratory Vacuum:
--
Sanitary Drain:
Yes
acrylic prismatic lens, W/3-F32T8
Reagent Grade Water:
--
lamps, 3500K, CRI=75
Medical Air:
Yes
(minimum)
Medical Vacuum:
Yes
3. 600mm x 600mm (2' x 2')
Oxygen:
--
Notes: 1. Potential cold water is required for
acrylic prismatic lens, W/3-FB31
laser equipment. (Coordinate with
lamps, 3500K, CRI=75
equipment supplier.)
(minimum)
POWER
General:
Emergency:
Notes: 1. Special receptacle for laser
equipment. (Coordinate with
supplier).
COMMUNICATION
ADP:
--
Radio:
--
Telephone:
Yes
Intercom:
--
Pub. Addr:
--
Notes:
1.Nurse Call
VA DESIGN GUIDE
AMBULATORY CARE INVASIVE PROCEDURES SUITE
PAGE 5-4