First Draft 3-15-97
Design Standards
Special Procedures / Bronchoscopy Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Dry Bulb Temp Cooling:
24C (76F)
Ceiling Ht:
2900mm (9'-6")
25C (78F)
Wall Finish:
Vinyl Wall Covering
Minimum % Outside Air:
--
Wainscot:
--
100% Exhaust Air:
Yes
Base:
Resilient base
Noise Criteria:
NC-40
Floor Finish:
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
50%
Notes:
1. 900mm (3'-0") wide entry door
Relative Humidity/Heating:
30%
with
Minimum Air Changes/Hr.:
8
200 mm x 250mm (8" x 10")
Room Pressure:
Negative
tempered glass view window.
AC Load Lighting:
86 w/sm (8w/sf)
SPECIAL EQUIPMENT
AC Load-Equipment:
22 w/sm (2w/sf)
None
Number of People:
3
Special Exhaust:
--
LIGHTING
General:
70 FC
accomplished via low level outlets.
Special:
--
2. Provide a special hood and
Notes: 1. 20mm x 1200mm (2' x 4')
fumes if instrument cleaning is
acrylic prismatic lens, W/3-F32T8
done here rather than a separate
lamps, 3500k, CRI+75
room.
(minimum)
3. If Bronchoscopy room is used for
tuberculosis patient exams min.
dimmer.
air changes per hr. increases to
12 and provide filtration as per TB
POWER
Criteria in HVAC Design Manual
General:
for Hospitals Projects.
Emergency:
PLUMBING AND MEDICAL GASES
Notes:
1. Special receptacle for mobile
Cold Water:
Yes
fluoroscopy unit. (Coordinate with
Hot Water:
Yes
system supplier).
Laboratory Air:
--
2. Receptacle for crash cart to be on
Laboratory Vacuum:
--
emergency power.
Sanitary Drain:
Yes
COMMUNICATION
Reagent Grade Water:
--
ADP:
Yes
Medical Air:
Yes
Radio:
--
Medical Vacuum:
Yes
Telephone:
Yes
Oxygen:
Yes
Intercom:
Yes
Notes:
Pub. Addr:
--
Notes: 1. Junction box for CCTV camera
with conduit to adjacent diagnostic
room.
2. Junction box for poly somnograph
cabling with conduit diagnostic
room.
3. Nurse call system.
VA DESIGN GUIDE
AMBULATORY CARE INVASIVE PROCEDURES SUITE
PAGE 5-2