First Draft 3-15-97
Design Standards
Cystoscopy Room
ARCHITECTURAL
CONDITIONING
Ceiling:
Plaster
Dry Bulb Temp Cooling:
190 C( 68F)
Ceiling Ht:
2900mm (9'-6")(see note 1)
230C(75F)
Wall Finish:
Plaster
Minimum % Outside Air:
100
Wainscot:
--
Yes
Base:
Welded Seamless Flooring
Noise Criteria:
NC-40
Floor Finish:
Welded Seamless Flooring
Steam:
--
Slab Depr:
--
Relative Humidity/Cooling:
55%
Notes: 1. Additional 8" accessible space
Relative Humidity/Heating:
50%
above ceiling for microscope or
Minimum Air Changes/Hr.:
15 Occupied
10'-2"
8 Unoccupied
SPECIAL EQUIPMENT
Room Pressure:
Positive
None
AC Load Lights:
91W/m 2 (8.5W/SF)
AC Load Equipment:1
19W/m 2 (11.1W/SF)
LIGHTING
Number of People:
12
General:
2152lx(200 fc)(see note 1)
--
Special:
Surgical Light(see note 2)
Notes:
Emergency: 50% Gen. Fluorescent(see note 3)
PLUMBING AND MEDICAL GASES
Notes:
Cold Water:
Yes
color temperature of surgical light.
Hot Water:
--
2. (1) TYPE 840A, 1500 W
Laboratory Air:
--
3. Battery backup in (4) fixtures.
Laboratory Vacuum:
--
POWER
Sanitary Drain:
Yes
General:
(1) Module each wall
Medical Air:
Yes
Special:
(2) 7-1/2 KVA 12-Circuit IPU
Medical Vacuum:
Yes
Emergency:
Each IPU & X-Ray unit
Oxygen:
Yes
(1) Film Processor per Suite
Yes
Yes
COMMUNICATION
Anesthesia Evac:
Yes
Patient Monitor:
Yes
Notes:
--
Nurse Call:
--
Code One:
--
CCTV:
Empty Conduit
Telephone:
Wall Mounted Hand Free
Intercom:
Part of Telephone
Pub. Addr:
Empty Conduit
ADP:
Empty Conduit
Radio:
Empty Conduit
VA DESIGN GUIDE
AMBULATORY CARE INVASIVE PROCEDURES SUITE
PAGE 5-1