26 February 1993
Control Booth
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
25 NSF
Wall Finish
CMU (SC)
AC Load Lights
8.5 W/SF
Ceiling
PL
Wainscot
-
AC Load Equipment
65.0 W/SF
Ceiling Height
9'-6"
Base
ERF
Number of People
1
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
(0)
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
8 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
Lighting
Power
General
10 FC, 0.5 W/SF*
General
-
Special
-
Special
**
Emergency
-
Emergency
-
Notes:
*LIGHTING ON DIMMER
PLUMBING AND MEDICAL GASES
Sanitary Drain
-
Cold Water
-
**X-RAY MACHINE: 100 A, 208 V, 3 PHASE CIRCUIT BREAKER
Acid Waste
-
Hot Water
-
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
WALL MTD
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 6-7