26 February 1993
Radiographic Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
220 NSF
Wall Finish
CMU (SC)
AC Load Lights
4.9 W/SF
Ceiling
PL
Wainscot
-
AC Load Equipment
4.9 W/SF
Ceiling Height
9'-6"
Base
ERF
Number of People
3
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
YES
Room Pressure
POSITIVE
Dry Bulb Temp Cooling (F)
76
78
Minimum Air Changes per Hour
8 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
Lighting
Power
General
0.5-1.5 W/SF*
General
-
Special
-
Special
-
Emergency
-
Emergency
-
Notes:
*10 FC INCANDENSCENT ON DIMMER, 30 FC FLUORESCENT
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
Acid Waste
-
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
WALL MTD
ADP
EMPTY CONDUIT
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
EMPTY CONDUIT
Notes:
Public Address
EMPTY CONDUIT
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 6-6