26 February 1993
Animal Surgical Preparation Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
120 NSF
Wall Finish
CMU (SC)
AC Load Lights
6.7 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
9.2 W/SF*
Ceiling Height
9'-0"
Base
ERF
Number of People
3
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
POSITIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
4 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
-
NONE
Steam
-
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*EXAM LIGHT INCLUDED AS EQUIPMENT LOAD
Lighting
Power
General
100 FC, 5.0 W/SF*
General
700 W
Special
**
Special
-
Emergency
50% GEN FLUOR
Emergency
-
Notes:
*COLOR CORRECTED FLUOR LAMPS
PLUMBING AND MEDICAL GASES
**(1) SURGICAL LAMP, SINGLE HEAD
Sanitary Drain
YES
Cold Water
YES
Acid Waste
-
Hot Water
YES
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
WALL MTD
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
PART OF TELEPHONE
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 6-2