26 February 1993
Clean Cage Storage Room
Design Standards
ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
Floor Area
405 NSF
Wall Finish
CMU (SC)
AC Load Lights
1.6 W/SF
Ceiling
PCP
Wainscot
-
AC Load Equipment
1.2 W/SF*
Ceiling Height
9'-0"
Base
ERF
Number of People
3
Slab Depression
-
Floor Finish
ERF
Noise Criteria
NC-40
Notes:
Lead Lining
-
Room Pressure
POSITIVE
Dry Bulb Temp Cooling (F)
78
72
Minimum Air Changes per Hour
4 (SA)
Minimum % Outside Air
100
YES
SPECIAL EQUIPMENT
YES*
VS-261 STERILIZER
Steam
YES*
Relative Humidity - Cooling
50 %
Relative Humidity - Heating
30 %
Notes:
ELECTRICAL
*VS-261: SEE H-08-6 FOR STEAM, HEAT GAIN, EXH CAPACITIES
Lighting
Power
General
20 FC, 1.0 W/SF
General
900 W
Special
-
Special
*
Emergency
-
Emergency
-
Notes:
PLUMBING AND MEDICAL GASES
Sanitary Drain
YES
Cold Water
YES
*VS-261: 25 A, 120 V
Acid Waste
-
Hot Water
-
Silver Recovery
-
Reagent Water
-
Medical Air
-
Laboratory Air
-
Medical Vacuum
-
Laboratory Vacuum
-
Oxygen
-
Fuel Gas
-
Telephone
-
ADP
-
Nitrous Oxide
-
Anesthesia Evac
-
Intercom
-
Radio
-
Notes:
Public Address
-
Other
-
Notes:
VA Design Guide -- Veterinary Medical Unit
Guide Plate 5-14