Technical Requirements -
Telephone/Data Spaces & Cable Pathways
DETAIL A
Telephone Equipment Room Pull Box - Ceiling mount
Note: Conduit should be installed
to facilitate access to pull box for
wiring and shall not interfere with
Pull Box
access to plywood backboards
or equipment.
Top 4 - 4" conduits
to T/D closet #1
Caution: Do not block
with sprinkler, electrical or
other piping or ductwork.
Note: This pull box may be
located in Computer room or
Bottom 4 - 4"
between Equipment Room and
Computer Room if access is a
conduits to T/D
problem.
closet #2
3 ea.. - 4" conduit from Computer Room
sub floor
4 ea.. - 4" conduits from Telephone Equipment Room
Page 4-20
VBA Design Guide