Technical Requirements -
Computer Room
should plan to utilize their existing UPS and PDU if they are serviceable and
adequate for the load.
Should new or replacement units be required, the following list of desirable
attributes or better should be specified to provide the protection and versatility that
VBA computer room systems require:
The UPS shall be sized based on the equipment requirements of the Regional
Office and future anticipated growth. The attached load should not be less than
30% of the UPS capacity and not more than 70% capacity for the initial sizing.
Less than 30% results in significantly decreased efficiency and greater than
70% allows little room for future growth. In general, 50% - 70% load should be
the goal on sizing the UPS.
Battery systems should be sized to allow for 20 minutes of battery backup or
more at full rated output.
Input filter
Input isolation transformer (may be combined with input filter and step-down
Preferably 480V input / 120/208V output 3 phase delta / wye, 4 wire. 120/208V
input & output acceptable dependent on pricing.
Full, "on-line" solid state conversion (rectifier/inverter)
IGBT technology preferred. SCR technology is acceptable
Static bypass / automatic transfer to bypass on failure, overload or battery end of
life.
Monitor / alarm panel with power parameters, alarms, alarm history (discharge
record and battery monitor desirable)
Maintenance Bypass Switch / circuit - Internal (by UPS manufacturer) or external
(by electrical contractor or VA/GSA electricians) This feature allows continued
operation on utility power when unit is down for service.
Minimum 1 year parts and labor on complete system plus battery manufacturers
warranty to be provided to VA IRM.
Electrical Power Off (EPO) capability to interface with EPO pushbuttons at exit
doors and smoke detection system / pre-action sprinkler system (if installed).
Include shipping, placement and startup in quote from UPS vendor.
Electrical power to UPS by electrical contractor, GSA or VA.
Electrical wiring to PDU and from PDU to receptacles by electrical contractor,
GSA or VA.
The UPS shall have dry contacts available for external alarm and control and
specifically have at least one form "c" contact to signal computer equipment that
the UPS is on battery.
Server shutdown software and hardware/cable connectivity should be provided.
Page 4-6