Technical Requirements -
Computer Room
Applicable Standards
The following standards and codes, as applicable, shall be adhered to by the
design team and installation contractors:
1. National Fire Codes NFPA latest revision, applicable sections including but
,
:
not limited to the following:
A. National Electrical Code - NFPA 70
B. Electronic Computer / Data Processing Equipment - NFPA 75
C. National Fire Alarm Code - NFPA 72
D. Life Safety Code - NFPA 101
2. The BOCA National Building Codes
3. Federal Information Processing Standard (FIPS PUB 94)guideline on
-
electrical power for ADP installations.
4. VA Master Construction Specificatns (must be made project specific and
io
adhere to these guidelines)
5. Americans with Disabilities Act (ADA) or Uniform Federal Accessibility
Standards (UFAS)
6. VBA/IRM Directive No. 5.0.01, "Information Security Program , M 0-4,
" 2
Part II.
7. VA HVAC Design Guide
Partitions
Partitions shall be in accordance with NFPA 75 and the above codes. Walls shall
be painted or otherwise covered to provide a vapor barrier in order to maintain
stable humidity level within the room.
Doors
The computer room shall have a minimum of two (2) doors, 48 inches wide, on
opposite ends of the room that are of the out-swing variety. At least the ramp door
must exit directly into a corridor. A third door may be provided to allow direct
Page 4-2
VBA Design Guide