HEATING, VENTILATING AND AIR CONDITIONING
ARCHITECTURAL
AC Load Lights
9.8 W/SF
800 NSF (74.40 NSM) Wall Finish GYP. BOARD(SC)
Floor Area
ACROVYN ON CBB
Ceiling
GYP. BOARD(SC)
Wainscot
AC Load Equipment
11.0 W/SF
Ceiling Height 10-0"* (3.0 METERS) Base
Number of People
20
INTEGRAL 6" (152 mm)
COVE BASE
Noise Criteria
NC-40
Floor Load
100 PSF
WSF
Floor finish
Room Pressure
POSITIVE
Note:
Lead Lining -
Dry Bulb Temp Cooling (Range)
62-80F (17-27C)
Refer to PG-18-1 and PG-18-6
62-80F (17-27C)
*ADDITIONAL 8" (203 MM) ACCESSIBLE SPACE ABV CLG FOR
Minimum Air Changes per Hour
20 OCC/8 UNOCC
Minimum % Outside Air
100
MICROSCOPE OR 10'-2" (3.05 METERS)
YES
-
ELECTRICAL
Steam
-
Lighting
Power
Relative Humidity Range
45-55 %
Relative Humidity Range
45-55 %
General
200 FC, 6.0 W/SF*
General
(1) MODULE EA WALL
Special
SURGICAL LIGHT**
(1) MODULE EA COLUMN
Emergency
50% GEN FLUOR***
(2) LASER OUTLETS
Special
****
Emergency
PLUMBING AND MEDICAL GASES
*****
*COLOR IMPROVED FLUOR LAMPS MATCHING COLOR TEMPERATURE
YES
YES
Cold Water
Medical Air
OF SURGICAL LIGHT
YES
YES
Hot Water
Medical Vacuum
**(2) TYPE B, 1500 W
Oxygen
YES
Sanitary Drain
YES
***BATTERY BACKUP IN (10) FIXTURES
Nitrous Oxide
-
Acid Waste
YES
****(2) 7-1/2 KVA 12-CIRCUIT IPU
YES
Silver Recovery
-
*****EACH IPU & X-RAY UNIT, (1) FILM PROCESSOR PER SUITE
Anesthesia Evac
YES
TELECOMMUNICATIONS
Patient Monitor
YES
Data
WALL TERMINAL
SPECIAL EQUIPMENT
-
@ EACH UTIL. COL.
Nurse Call
Telephone
WALL MTD HAND FREE
Code One
YES
None
@ EACH UTIL. COL.
EMPTY
CCTV
CONDUIT
COMB. W/TELEPHONE
Intercom
Public Addr.
EMPTY CONDUIT
ADP
EMPTY CONDUIT
Radio
EMPTY CONDUIT
Design Guide - Surgical Service
Design Standards
Special Purpose Operating Rm
Guide Plate:
4-2h
MAX: 800 NSF (74.40 NSM)
MIN: 600 NSF (55.80 NSM)
MIN: 700 NSF (65.10 NSM) CARDIAC
Date: August 2005