ARCHITECTURAL
HEATING, VENTILATING AND AIR CONDITIONING
GYP. BOARD(SC)
Floor Area
650 NSF (60.45 NSM)
Wall Finish
AC Load Lights
8.5 W/SF
ACROVYN ON CBB
Ceiling
GYP. BOARD(SC)
Wainscot
AC Load Equipment
13.7 W/SF
Base
10'-0" (3.0 METERS)
INTEGRAL 6" (152 mm)
Ceiling Height
Number of People
12
COVE BASE
Floor Load
100 PSF
Noise Criteria
NC-40
WSF
Floor finish
Room Pressure
POSITIVE
Note:
Lead Lining
TO BE DETERMINED
Dry Bulb Temp Cooling (Range)
62-80F (17-27C)
Refer to PG-18-1 and PG-18-6
SEE NOTE 3, GP 4-1b
62-80F (17-27C)
Minimum Air Changes per Hour
20 OCC/8 UNOCC
*ADDITIONAL 8" (203 mm) ACCESSIBLE SPACE ABV CLG FOR
Minimum % Outside Air
100
MICROSCOPE OR 10'-2" (3.05 METERS)
YES
-
ELECTRICAL
Steam
-
Lighting
Power
Relative Humidity Range
45-55 %
Relative Humidity Range
45-55 %
General
200 FC, 6.0 W/SF*
General
(1) MODULE EA WALL
Special
SURGICAL LIGHT**
Emergency
50% GEN FLUOR***
COLUMN
(2) LASER OUTLETS
Special
PLUMBING AND MEDICAL GASES
****
Emergency
*****
YES
Cold Water
Medical Air
YES
*COLOR IMPROVED FLUOR LAMPS MATCHING COLOR TEMPERATURE
YES
Hot Water
Medical Vacuum
YES
OF SURGICAL LIGHT
Oxygen
YES
Sanitary Drain
NO
**(AR) TYPE B, 1500 W
Acid Waste
-
Nitrous Oxide
YES
***BATTERY BACKUP IN (8) FIXTURES
Silver Recovery
-
YES
****(2) 7-1/2 KVA 12-CIRCUIT IPU
Anesthesia Evac
YES
*****EACH IPU & X-RAY UNIT, (1) FILM PROCESSOR PER SUITE
SPECIAL EQUIPMENT
TELECOMMUNICATIONS
None
Patient Monitor
YES
Data
WALL TERMINAL
-
@ EACH UTIL. COL.
Nurse Call
Telephone
WALL MTD HAND FREE
Code One
YES
@ EACH UTIL. COL.
EMPTY
CCTV
CONDUIT
COMB. W/TELEPHONE
Intercom
Public Addr.
EMPTY CONDUIT
ADP
EMPTY CONDUIT
Radio
EMPTY CONDUIT
Design Guide - Surgical Service
General Operating Room
Guide Plate:
Design Standards
4-1h
Date: August 2005