September 30, 1994
Design Standards
Preparation, Assembly & Sterilization Area
ARCHITECTURAL
Ceiling
AT (SP)
Wainscot
-
Ceiling Height
2700 (9'-0")
Base
QT
Wall Finish
PL (SC)
Floor Finish
QT*
Notes:
Slab Depression -
*EXTEND QT 10' BEYOND STERILIZERS
SPECIAL EQUIPMENT
ELECTRICAL
Lighting
Power
General
50 FC - 3 W/SF
General
Special
-
Emergency
-
Notes:
ADP
-
Telephone
-
Radio
YES
Intercom
EMPTY CONDUIT
Notes:
Public Address -
HEATING, VENTILATING AND AIR CONDITIONING
Dry Bulb Temp Cooling F
76
Relative Humidity/Cooling 50%
Minimum % Outside Air
100
Minimum Air Changes/Hr
10
YES
Room Pressure
POSITIVE
Noise Criteria
NC-40
AC Load - Equipment
0.4645.W/SM
Steam
-
Number of People
2
Notes:
-
PLUMBING AND MEDICAL GASES
Cold Water
YES
Sanitary Drain
YES
Hot Water
YES
Reagent Grade Water
-
Laboratory Air
-
Medical Air
-
Laboratory Vacuum
-
Medical Vacuum
-
Other
-
Oxygen
-
Notes:
VA Design Guide -- Supply, Processing, & Distribution
Guide Plate 5-2