Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Lithotripsy Room/Control Room 28-B
Function:
This space is intended to provide the capabilities for Lithotripsy procedures. This space is part of the GU
Clinic and should be in proximity to the Cystoscopic Room. It may share a common control/processing
area with a Cystoscopic Room.
Space Requirement:
400 NSF
Architectural:
Finish Code:
9-A
Floor Finish:
Resilient Sheet*
Base:
Resilient Sheet*
Wall Finish:
Plaster/Special Coating**
Ceiling:
Plaster/Paint
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
has been selected.
See SD 08110-3.DWG, 13091-1.DWG and 13091-2.DWG.
Membrane waterproofing required at floor drain.
Hardware:
106
Doors:
4'-0" x 7'-0" wood, lead lined, optional lead glass view panel.
Windows:
None
*Heat-Welded Seams, see Mspec #09666
**See Mspec #09815
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: 6
Min. % Outside Air:
15%
Pressure:
Positive
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
5100w
Equipment: 3500w*
People:
800w, sensible
1040w, latent
Plumbing:
Provide Regent Grade Water Supply as per manufacturer's requirements.
Electrical:
Lighting Levels:
Gen. Illum: 200fc
Emergency Power:
Nurse Call
Office of Facilities Management
162