Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Exam/Treatment 27
Function:
This space is intended to provide for the examination of SCI Outpatients. It should be adjacent to the
Physician's Office.
Space Requirement:
170 NSF
Architectural:
Finish Code:
1-BB
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Lay-in Gypsum Panels/Paint
Ceiling Height:
9'-0"
Noise (STC Rating):
40
Slab Depression:
None
Special Construction:
-
Hardware:
53
Doors:
4'-0" x 7'-0" wood or metal
Windows:
None Required
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Positive
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
35
A/C Loads:
Lights:
600w
Equipment: 450w
People:
150w, sensible
150w, latent
Electrical:
Lighting Levels:
High: 100 fc
Low: 50 fc
Emergency Power:
One Ceiling Light
One Receptacle (near bed)
Nurse Call
Medical Gases
Office of Facilities Management
152