Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Dishwash 20-A
Function:
This space is intended to be contiguous to a Full Serving Line in order to allow the maintenance of
dinnerware to be localized.
This space is required when there are more than 60 SCI beds.
Space Requirement:
200 NSF
Architectural:
Finish Code:
3-A
Floor Finish:
Quarry Tile (slip-resistant)
Base:
Quarry Tile
Wall Finish:
Ceramic Tile
Ceiling:
Acoustical Tile/Special-Faced
Ceiling Height:
9'-0"
Noise (STC Rating):
45
Slab Depression:
4" quarry tile, with slope to drain.
Special Construction:
-
Hardware:
Cased opening only
Doors:
-
Windows:
None
HVAC:
Temperature:
Summer: 82
Winter:
70
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
30%(PF)
Noise Criteria:
50
A/C Loads:
Lights:
-
Equipment: -
People:
-
Steam:
See HVAC Note 5
Electrical:
Lighting Levels:
Gen. Illum: 50fc
Emergency Power:
-
Office of Facilities Management
120