Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Patient Laundry Room 16
Function:
This space is to provide an easily accessible area on the Nursing Unit for patients to wash their personal
clothing.
Space Requirement:
72 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
8'-0"
Noise (STC Rating):
35
Slab Depression:
None
Special Construction:
-
Hardware:
23
Doors:
4'-0" x 7'-0" wood or metal, optional glass view panel.
Windows:
None
HVAC:
Temperature:
Summer: -
Winter:
82
Min. Air Changes/Hour:
Min. % Outside Air:
-
Pressure:
Negative
% Filtration:
30%(PF)
Noise Criteria:
50
A/C Loads:
Lights:
-
Equipment: -
People:
-
Electrical:
Lighting Levels:
Gen. Illum: 50fc
Emergency Power:
Nurse Call
Office of Facilities Management
105