Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Day Room 15
Function:
This space is intended to accommodate a variety of unsupervised recreational activities among patients
and on occasion patients and family.
Space Requirement:
12.5 NSF/Bed
Architectural:
Finish Code:
1-G
Floor Finish:
Base:
Vinyl
Wall Finish:
GWB/Vinyl Fabric Wallcovering
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
35
Slab Depression:
None
Special Construction:
-
Hardware:
5
Doors:
2@3'-0" x 7'-0"
Wood or metal, upper half=laminated safety glass.
Windows:
Desirable, see H-08-3, CS-31-1 & CD-35.
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: 12 (100% Exhaust)
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
1320w
Equipment: 600w
People:
1350w, sensible
1350w, latent
Electrical:
Lighting Levels:
Three Level Fluorescent:
High: 60fc
Med: 45fc
Low: 20fc
Incandescent Wall-Washers on Dimmer: 0fc-5fc
Emergency Power:
One Ceiling Light
Nurse Call
Office of Facilities Management
102