Spinal Cord Injury Center Design Guide
July 1990 (Rev. Jan. 2004)
Function:
This space is intended for the secure storage of all the medications assigned to the nursing unit and for
the storage of those medical supplies (i.e. syringes) that also require secure storage. This space must be
Space Requirement:
120 NSF
Architectural:
Finish Code:
1-A
Floor Finish:
Base:
Vinyl
Wall Finish:
Gypsum Wallboard/Paint
Ceiling:
Acoustical Tile
Ceiling Height:
9'-0"
Noise (STC Rating):
30
Slab Depression:
None
Special Construction:
Reinforced Wall to accept Modular C-lockers.
Hardware:
13
Doors:
3'-0" x 7'-0" wood or metal
Windows:
None
HVAC:
Temperature:
Summer: 72@50%RH
Winter:
82@30%RH
Min. Air Changes/Hour: None (see HVAC Note 3)
Min. % Outside Air:
15%
Pressure:
Negative
% Filtration:
30%(PF)/85%(AF)
Noise Criteria:
40
A/C Loads:
Lights:
240w
Equipment: 350w
People:
75w, sensible
75w, latent
Electrical:
Lighting Levels:
Gen. Illum: 70fc
Emergency Power:
Receptacle
Refrigerator
Office of Facilities Management